5.2.5 Output 1
Output 1 may be fitted with a relay (form A), or SSR drive (logic) output depending on the order code. The function of the output may be selected from a list of options including heat or cool outputs for the control loop, or alarms or events which may be used for external indication.
P11
|
Select P11 to configure Output 1 (OP1).
|
|
The code can be checked against the label on the side of the controller. |
|||
nonE |
Output disabled |
|
||||
Heat |
Heat output (factory default) |
Output 1 controls the heating power demand. The sense is set to normal – the state of the output is shown in the table. This is the usual setting for control outputs. |
|
OP1 State when heating |
||
Relay |
Energised |
|||||
Logic |
ON |
|||||
|
||||||
CooL |
Cool output |
Output 1 controls the cooling demand. The sense is set to normal – the state of the output is shown in the table. This is the usual setting for control outputs. |
|
OP1 State when cooling |
||
Relay |
Energised |
|||||
Logic |
ON |
|||||
|
||||||
AL1 |
Alarm 1 |
Output 1 will operate as shown in the table if the alarm selected is active. |
|
Alarm active |
||
AL2 |
Alarm 2 |
Relay |
Energised |
|||
AL3 |
Alarm 3 |
Logic |
ON |
|||
|
||||||
AL1. i |
Alarm 1 inverted. |
Output 1 will operate as shown in the table if the selected alarm is active. This is the normal setting for alarms since if power to the controller fails an alarm state will be indicated by a powered external device. |
|
Alarm active |
||
AL2. i |
Alarm 2 inverted |
Relay |
De-energised |
|||
AL3. i |
Alarm 3 inverted |
Logic |
OFF |
|||
|
||||||
t.End |
Timer end status |
OP1 can be used to operate an external device to indicate when the timer has timed out. A relay is energised or a logic output is ON when the timer has timed out. |
|
Timer Operation is described in section 4.11. |
||
t.rUn |
Timer run status |
OP1 can be used to operate an external device to indicate when the timer is running. A relay is energised or a logic output is ON when the timer is running. |